991/991N Installation Instructions

Updated Mar 26, 2026

991/991N Installation Instructions

Switch Information

Time Adjustment Procedure:An image of the time adjustment screw location

  1. Use fingers to turn the brass adjustment screw.
  2. Turn clockwise to increase the delay.
  3. Tun counterclockwise to decrease delay. 
  4. Like all pneumatic switches, time delays are approximate and can be affected by environmental variables. If in doubt, leave a longer delay to allow sufficient egress time. 

Note: The adjustment screw may be facing up or down.

Specifications:

Time Range Standard and Narrow 1 sec to 45 sec +/- 15%
Repeated Accuracy +/- % @ 72°F (22° C)
Switch Rating 5 Amp @ 125 VAC
Temperature Range -17°F to +120°F (-27°C to +49°C)
Timer Life 1 million operations

Hardware Installation

The 991 mounts in a single-gang electrical box with 2 screws. Slotted screws require a standard screw driver. Carefully line up these screws with tans in the electrical box and tighten.

The 991 narrow pushbutton includes a 1/4" filler plate for use in installations as required. 

Typical System Control Wiring Diagrams

Electromagnetic Lock, Normally Closed Circuit

An image of the Electromagnetic Lock, Normally Closed Circuit

Electronic Strike, Normally Open Circuit

An image of the Electronic Strike, Normally Open Circuit