DE - Delayed Egress Wiring Instruction and Specifications

Updated May 5, 2026

This article provides complete resources for the Delayed Egress system.
It includes wiring instructions, features, and specifications.

DELAYED EGRESS

Delayed Egress

Instructions

Document ID Description
T93668 DE Template – Door and Frame Installation
T93668_SP Instalación de puerta y marco con dispositivo de salida retardada (Spanish)
T93668_FR Installation du dispositif de sortie retardée sur la porte et le cadre (French)
T93654 DE Installation Instructions and User Guide
T93654_SP Dispositivos de salida con salida retardada instrucciones de instalación eléctrica (Spanish)
T93654_FR Dispositifs de sortie retardée instructions pour l’installation électrique (French)
T93667 PS161 Power Supply (6 Amp) Instructions
T93667_SP Fuente de alimentación PS161-6
Instrucciones de instalación
T93667_FR Alimentation électrique PS161-6
Instructions d’installation

Specification

APEX 2000 Delayed Egress, DE, Specifications

  • The Delayed Egress (DE) Exit Device provides a controlled egress for openings which require Panic or Fire Exit Hardware for safe egress. 
  • It is a self contained exit device, which when armed will deny exit to unauthorized personnel for 15 or 30 seconds, while simultaneously sounding a local or remote audible alarm.
  • The Remote Monitoring feature will alert the security personnel that an attempt is being made to exit the opening. After the 15 (or 30) second delay of egress period the device will function as a standard exit device for safe egress.

Operations

  • The device secures the door in the locked mode with the Red LED indicating locked status.
  • Depressing the Touchbar by accident or for less than the Nuisance Delay Time will sound the alarm without initiating the alarm sequence.
  • Depressing the Touchbar with less than 15 pounds pressure, for longer than the Nuisance Delay Time will initiate an irreversible local audible beeping tone and a visual Red indicator until the device releases.
  • After the delayed egress time, the lock releases and the alarm changes to a steady tone which continues to alarm until reset.
  • The remote monitoring contact output can be used to alert security personnel.
  • When a person depresses the Touchbar, egress is delayed for 15 or 30 seconds and security personnel are alerted for response.

Trim

  • All standard device trims and functions are available, including "03" function
  • Trim Lock/Unlock will function normally even when the delayed egress feature is armed.
  • The Device will only be affected when the Touchbar is depressed from the inside.
  • All (DE) Rim and Mortise Devices are also available with Electric Lock/Unlock for the outside Trim.
  • Available for all Apex Series Exit Devices.
  • The Delayed Egress Devices are manufactured and tested to exceed ANSI 156.3 and 156.24.
  • Devices are UL Listed as a Controlled Exit Device (FULA) and Special Locking Arrangements (FWAX) category.
  • Meets all requirements of NFPA 101.
     

Features

Fire Alarm Contacts Fire Alarm input at any time will cut power to the delayed egress function and provide immediate egress. 
Armed-Momentary Egress Turning the key clockwise allows authorized personnel to exit without alarming. At the end of the field selectable time period (10, 20 or 30 seconds), the device will relock and rearm.
Device Networking Feature This feature allows a Delayed Egress device to arm, alarm, reset and disarm all devices on the same circuit. Each device will continue to operate independently for Momentary Egress.
30 Seconds Delay A 30 second delay option is available. A written approval from the authority having jurisdiction is required. Note: A "30 Second" decal is provided when the 30 Second Delay option is specified.
Nuisance Delay Time A Nuisance Delay Time helps avoid inadvertent activation. The alarm will sound when the Touchbar is pressed, but the alarm sequence will not start unless the touch bar is held in for more than the Nuisance Delay Time. Delay Time is field selectable for 0, 1, 2 or 3 seconds.
Integral Key Switch
  • Arm: The Key switch provides the means to locally arm the (DE) device.
  • Momentary Egress : The Key switch will provide temporary disarming to allow for momentary egress (10, 20 or 30 seconds) when the device is in the armed state. The Key switch will Disarm the device and it will function as a standard exit device. 
  • Reset: During alarm sequence the device can be rearmed by the Key Switch.
  • Requires the use of a 1-1/4 mortise cylinder, not furnished standard. Specify when required.
Led Status Indicator A color coded LED indicates Arm, Disarm and Alarm status.
Flashing Green : Arming
Flashing Red : Armed
Green : Unarmed
Red : Alarmed
Off : No Power to Device (Normal Exit)
Internal alarm The device has an 85 dB horn that sounds until the device is reset.
External Alarm A set of relay contacts rated at (1 amp, 24VDC) are provided for activating external local or remote audible/visual signaling devices.
External Inhibit Arm/Rearm : Accepts a contact to Arm/Rearm the device.
Momentary Egress : Accepts a contact to provide temporary disarming to allow for momentary egress when the device is in the armed state. The Momentary Egress will be engaged as long as the switch closure is maintained.
Reset : Accepts a contact to reset the device during alarm.
Door Position Switch

Used in conjunction with the Delayed Egress Exit Device, the following security features are added: 

  • The Exit Device Alarm will sound if the door is not closed when the device is armed. 
  • The Alarm will sound if the door is forced open when the device is armed. 
  • While the device is in the arming stage you may exit the opening. 
  • When the door closes the arm/rearm time is cut short and the device is armed preventing unauthorized tailgating through the opening.

PS161-6 Power Supply

  • The PS161-6 Power Supply is designed as a power source for a variety of applications including Electric Locking, Exit Alarm and Delayed Egress Exit Devices.
  • The Power Supply is a 120V input with a 12 or 24V output rated at 6A. 
  • It can control up to 4 delayed egress exit devices. 
  • Note: Adding additional loads to the PS161-6 Power Supply (i.e., Card readers, Horns, etc.) may reduce the quantity of Delayed Egress Exit Devices controlled by the power supply.
  • Unit is complete with power supply, enclosure, battery leads, and lock.
  • LED indicators for AC Input, DC output, and battery backup status.

PS161-6 Power Supply Specifications

Input

  • Voltage: 120V AC, 60HZ 
  • Current: 3.5A AC 
  • Input fuse ratings: 5A/250V
  • AC input is protected via an automatic
    reset circuit breaker
  • Battery fuse ratings: 7.5A/32V

Output

Voltage: 12 or 24V
Total output: 6 amps
• Power limit/output: 2 amps/per channel
 Outputs: 8 (For Delayed Egress applications:
use only 4)
• Ripple voltage: 910mV (Filtered and regulated outputs)
• Protection: Thermal and short circuit protection with
auto reset overload protection.

Battery Backup Charger

Built-in charger for sealed lead acid or gel type
batteries (batteries not included)
• Maximum charge current: 1.54A
• Automatic switch over to stand-by is instantaneous with no interruption

Additional Features

Short circuit and overload protection.
Supervised Fire Alarm disconnect (latching or non-
latching) on a normally open (NO) or normally closed (NC) trigger.
 

DE Electrical Specifications

  • Voltage: 24VDC
  • Current Disarmed: 100 mAmps
  • Current Armed: 3.2 Amps for 200 ms, 200 mAmps steady state 

Door Widths

  • Available for 3'-0" and 4'-0" openings.
  • For openings 3-1" and greater, please specify door width requirements. 
  • Note: Not available for openings less than 3'-0" .
  • PS161-6 Power Supply Required for Delayed Egress Devices

Enclosure Dimensions

  • 12.5" x 13" x 3.25" (318mm x 330.2mm x 82.55mm)

Wire Chart and Ohm's Law

Minimum Wire Gauge for 24 volts AC or DC

  Distance in feet from power source to farthest locking device
Amps 25 50 75 100 150
6 18 16 16 14 12