YG80 Weatherproof Lock Configuration

Updated May 13, 2026

Wiring

Wiring Overview

The wires are part of a 3 metre sealed cable out of the YG80, the wires can be routed back to the power supply and any sensors or alarm systems. In the case of requiring a longer run, the wires can be extended as appropriate to the installation. Connect the wires as per the table below, where power and control are required for the YG80 to function, and all switch monitors are optional.

RED Positive + Positive connection to DC power supply Power (12 – 24V)
BLACK Negative - Negative connection to DC power supply
BLUE Control 1 Switched positive control input Control*
BROWN Control 2 Switched positive control input (Refer to article Operations Modes - Twin Wire Mode)
YELLOW Bolt Unlock Switch Normally open contact (NO), closed when the bolt pin is retracted
ORANGE Bolt Lock Switch Normally open contact (NO), closed when the bolt pin is extended
PURPLE Door Position Switch Normally open contact (NO), closed when the strike is aligned with the lock
GREEN Tamper Detection Switch Normally closed contact (NC), open when the lid is removed or wires cut
WHITE Switch Common Common contact for all the switch monitors

Fail Safe Connection (Normal Mode)

When wiring the YG80, the positive voltage is connected to RED, negative is connected to BLACK and a switched positive voltage wire connected to BLUE. In Fail Safe configuration applying voltage to the BLUE control wire signals it to lock. The lock signal in Fail Safe configuration is active high.

Fail Safe connection wiring diagram for YG80

Fail Secure Connection (Normal Mode)

When wiring the YG80, the positive voltage is connected to RED, negative is connected to BLACK and a switched positive voltage wire connected to BLUE. In Fail Secure configuration applying voltage to the BLUE control wire signals it to unlock. The lock signal in Fail Secure configuration is active low.

Fail Secure connection wiring diagram for YG80

Toggle Mode (And Twin Wire Mode)

When wiring the YG80, the positive voltage is connected to RED, negative is connected to BLACK and a switched positive voltage wire connected to BLUE (and BROWN for Twin Wire Mode). In Toggle Mode, applying a pulse to the BLUE control wire toggles between lock and unlock. In Twin Wire Mode, applying a pulse to the BLUE control wire triggers the YG80 to lock and applying a pulse to the BROWN control wire triggers the YG80 to unlock.

Toggle Mode and Twin Wire Mode wiring diagram for YG80

Dip Switch Positions

The operating configuration of the YG80 controls how the lock will function and there are several settings available. There are four dip switches on the printed circuit board with three being used to configure the lock and the fourth for diagnostic purposes. The dip switches are located on the top of the printed circuit board (pictured below) and can be set as per the following table.

Location of the four dip switches on the YG80 printed circuit board
Dip Switch # Setting Description
1 Operations Modes Set how the control line/s lock or unlock the YG80 (Refer to Article Operations Modes - Normal Mode)
2
3 Failures Modes Set whether the YG80 will lock or unlock on failure (Refer to Operation Modes - Toggle Mode)
4 Heater Modes Set whether the heater will activate at low temperatures. Use this setting when the ambient temperature can drop below 0°C (Refer to Operation Modes - Twin Mode)