Supply Voltage | 12VDC to 24VDC (NOTE: Status LED will blink red if |
|---|---|
Standby Current | 50mA maximum at 12VDC" |
Operating | 200mA maximum at 12VDC (with no external mechanical load applied to handle) |
Stall Current | 1A maximum at 12VDC (limited to 2 seconds) |
Operating | 1 second maximum (NOTE: Power must be present during transit times. If power is removed while the lock slide is in transit, it will complete it’s cycle when power |
Electronic | 3 seconds minimum |
Open | Rated for supply voltage, maximum load |
Alarm | 100mA/ output maximum |
Specifications
Package Contents
• 3525 Electromechanical Rack Handle Lock with Reader
• M3x25 Mounting Screws (qty 4)
• M3x14 Mounting Screw
• Rotation Limiter Standard
• Rotation Limiter - Extended (for thicker panels)
• Cam Bolt
• Top Mounting Bracket
• Bottom Mounting Bracket
• Installation Instructions
• Keys (qty 3)*
* For 3525 with SFIC, keys and cores are sold separately.
(NOTE: 6-pin cores must come with spacer.)
Reader | PRX | DFR | iCL |
|---|---|---|---|
Voltage | 12VDC ~24VDC | ||
Operating Current | 20mA | 125 mA | 60mA |
Transmit | 125 kHz | 13.56 MHz / 125 kHz | 13.56 MHz |
DATA Signal | 5VDC | ||
DATA Pulse | 40μs | ||
DATA Signal | 2ms | ||
Output Format | N/A | Reverse Byte Order (13.5MHz cards) Most Significant Bit First (125kHz cards) Upper and Lower Parity Bit Included | Reverse Byte Order with |
Overall | 8-1/4” H x 1-1/2” W x 1” D | ||
Handle Mounting 1. Assemble handle according to the proper handing required. | NOTES: |
Figure 3
Wiring
The 3525PRX/DFR/iCL contain two separate functional modules:
The reader modules read the contents of a compatible proximity
card and converts it to Wiegand format.
The actuator module controls and monitors the locking function of the
swinghandle.
These two modules operate independently of each other and require connection to an access
control unit (not provided), to be fully functional.
The reader modules of the swinghandle is accessed with a four pin connector attached to a harness connected to the module’s circuit board. The module’s connector pinout is:
Wire color | Description | Note |
|---|---|---|
Black | GND | Ground |
Red | Positive | 12 to 24 VDC Power Supply Input |
Green | DATA0 | DATA0 to Output |
White | DATA1 | DATA1 to Output |
The actuator module of the swing handle is accessed with a six pin connector on the rear of the unit, shown below.
Wire Color | Description | Note |
|---|---|---|
Black | GND | ground |
Red | Positive | 12 to 24 VDC Power supply Input |
Pin3 | N/C | no conenct |
Orange | Input Trigger | command input (9VDC up to supply voltage, 100 milliseconds minimum) |
Brown | Electronic Lock Status | Open collector output (sink to ground, 110 mA max. load) |
Blue | Mechanical Lock Status | Open collector output (sink to ground, 110 mA max. load) |
Input Trigger
This signal is used to control the electronic lock slide position.
For UNLOCKED position: Supply 9VDC minimum (do not exceed supply voltage) for at least 100 milliseconds. The lock will remain unlocked for as long as the signal is present, or a minimum of 3
seconds.
Signal timing can typically be adjusted through the access control device.
The input trigger current draw is less than 10mA.
Electronic Lock Status Output Signal
This output will provide a 100mA MAX sink to GND when the lock slide is electromechanically moved to the unlocked position.
Mechanical Lock Status Output Signal
This output will provide a 100mA MAX sink to GND when the handle is in the open position or when the keylock in the actuator is manually
unlocked.
Figures 5 & 6
1. Red & Black are 12 to 24 VDC input voltage.
2. Orange is a positive input with a Normally Open Switch. The lock will unlock for a minimum of 3 seconds on a momentary activation (50 millisecond minimum) or remain unlocked as long as the circuit is closed.
3. Blue is an alarm that will activate when the key is used to unlock the cabinet or anytime the handle is not seated and locked.
4. Brown is an alarm that will activate when the lock is electrically activated and will remain on until the lock electrically relocks.
Lock Status | Latch LED | Alarm Wires |
|---|---|---|
Secure | Steady Blue | Inactive |
Electrically Released | Blue/Magenta | Brown Active |
Mechanically Released | Blue Flashing | Blue Active |
Handle Not Fully Closed | Blue/Red Flashing | Blue/Brown Active |
Supply Voltage out of Spec | Flashing Red | N/A |
Industry Canada Statement
This device complies with Industry Canada license-exempt RSSs standard. Operation is subject to the following two conditions:
(1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment & receiver.
• Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
FCC Caution: To assure continued compliance, any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment. (Example - use only shielded interface cables when connecting to computer or peripheral devices). This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.