Answer
Note: Duress Mode (Silent Alarm) is not UL evaluated for either Display or Non-Display Keypads. Duress Mode (Silent Alarm) will only work if a LA GARD Series 700 Alarm Box is installed to Lock #1 BAT port.
- Duress Mode functions as a silent alarm that creates an external signal if a Duress Combination is entered.
- A Duress Combination is the User’s combination with the last digit entered one number higher or lower. For instance, a User Combination of 1-2-3-4-5-6-7-8 will use a Duress Combination of either 1-2-3-4-5-6-7-7 or 1-2- 3-4-5-6-7-9.
- When the Duress Combination is entered, a silent alarm will signal, and the lock will open. In multilock setup, alarm signals will emanate from the primary lock only.
Note: Combinations ending in 0 would use 1 or 9. Combinations ending in 9 will use 0 or 8.
Follow these steps to Enable/Disable Duress Mode on a 702 non-Display Keypad:
- Using the Keypad, input #14 + Master ID and Combination + Duress Mode (0 = Disabled, 1 = Enabled) + (←).
- The Keypad will beep three times and flash a green LED once complete.
|