DE8310/S User Guide

Updated Mar 26, 2026

This article explains how a DE8310/S Delayed Egress Maglock operates under normal, nuisance, exit, override, forced-open, fire alarm, and power-loss conditions, detailing the corresponding lights, buzzers, and alarm behaviors.

Normal Conditions

When the door is closed and locked.

System Status
 
Light Panel*
 
Local Buzzer 
(If Connected)
Local Alarm Relay Output
(If Connected)
Remote Alarm Relay Output
(If Connected)
Door Locked

Green

OFF

OFF

ON

Nuisance Period

Some installations have a short nuisance period set to accommodate accidental triggering. 
If the pressure on the door is withdrawn during the nuisance delay period, the system returns to normal conditions on its own. 

System Status
 
Light Panel*
 
Local Buzzer
(If Connected)
Local Alarm Relay Output
(If Connected)
Remote Alarm Relay Output
(If Connected)
Nuisance Delay Period

Blinking Red Light

Pulsing Sound

ON

ON

To Exit

If a Nuisance Delay is enabled, maintaining pressure past its time will start the irreversible release delay. If a Nuisance Delay is not enabled, slight pressure will start the irreversible release delay. The release delay time is posted on the door. Pressure is no longer required on the door. The lock will release when the delay period ends. The system now needs to be manually RESET using the key switch for the buzzer to stop.

System Status
 
Light Panel*
 
Local Buzzer
(If Connected)
Local Alarm Relay Output
(If Connected)
Remote Alarm Relay Output
(If Connected)
Release Delay Period

Blinking Red - slowly

Steady Sound

ON

OFF

 

Blinking Red & Green- slowly

Steady Sound
Until Reset

ON

OFF

To By-Pass the Delay Period and Exit

Manually OVERRIDE using the key switch to release the door. When the door closes, the system returns to normal conditions.

System Status
 
Light Panel*
 
Local Buzzer
(If Connected)
Local Alarm Relay Output
(If Connected)
Remote Alarm Relay Output
(If Connected)
Exit Switch to Open
(Authorized Exit)

Red

OFF

OFF

OFF

Door Forced Open

If this happens before the release delay period has lapsed, the buzzer indicators can only be turned off by switching the system power off.

System Status
 
Light Panel*
 
Local Buzzer
(If Connected)
Local Alarm Relay Output
(If Connected)
Remote Alarm Relay Output
(If Connected)
Forced Open

Blinking Red - Fast

Pulsing Sound

ON

OFF

When Testing the Fire System

The Fire Access Control Panel (FACP) function takes precedence over all inputs. The fire panel disconnect will cut the electrical power to the electromagnetic lock and the lock will release immediately. The light panel, buzzers and/or alarms will not function until the test is complete and power to the lock is restored. 

Power Outages

In the event of a power outage, the electromagnetic lock will release immediately. The light panel, buzzers and/or alarms will not function until power is restored. The mechanical door latch will keep the door closed and provide limited security. 

If door is closed when power is restored, the electromagnetic lock will function in the normal condition. If when the electrical power is restored to the electromagnetic lock and the door is open, the system only returns to normal conditions once door is closed. 

* The Light Panel color can be switched such that the red and green status is inverted. 

  • ON: Green LED light when unlocked - Red LED light when locked.
  • OFF: Red LED light when unlocked - Green LED light when locked (Default setting)