What hinge should I use with my electrified 9KW, 45HW, and IDH MAX (9KM/45HM)?

Updated Mar 7, 2026

Answer

The chart below can be used to guide your choice. It is recommended that you use 24 gage wire for power or double up 28 gage wires.

Wire Count

Device / Configuration Required Wire Count and Cable Suffix
9KW Power  2 wires (54 suffix if power is doubled up, or 66 suffix with 4 unused 28AWG wires)
9KW w/ RQE 4 wires (56 suffix if power is doubled up, or 66 suffix with 2 unused 28AWG wires)
45HW Power 2 wires (54 suffix if power is doubled up, or 66 suffix with 4 unused 28AWG wires)
IDH MAX Always has 2 power wires and 2 data wires = 56 Suffix (if you double up the power wires) or 66

You will need a 2 additional 28AWG wires if the following sensors are called out on your model number: 

  • RQE
  • DS
  • LS.
  • IDH* is a sensor option that would require 4 additional 28AWG wires)

*IDH = a sensor option for 45HW that adds both RQE and DS.

Applies To

45HW, 9KW, IDH MAX

Additional Information 

Electrical Ratings

Suffix Number of Wires Wire Gage Volts (AC or DC)
      6, 12, 24 48
      Current
-54 4 28 AWG 1 amp/wire 5 milli-amp/wire
-56 6 28 AWG .7 amp/wire 5 milli-amp/wire
-58 8 28 AWG .5 amp/wire 5 milli-amp/wire
-10 10 28 AWG .4 amp/wire 5 milli-amp/wire
-66 6 2 @ 24 AWG 2 amp/wire 5 milli-amp/wire
4 @ 28 AWG 1amp/wire 5 milli-amp/wire

Inrush 15 A for .05 second/wire

"CE" hinges are listed by UL at these ratings

*Not available in FBB168 and FBB199