Answer
The chart below can be used to guide your choice. It is recommended that you use 24 gage wire for power or double up 28 gage wires.
Wire Count
| Device / Configuration |
Required Wire Count and Cable Suffix |
| 9KW Power |
2 wires (54 suffix if power is doubled up, or 66 suffix with 4 unused 28AWG wires) |
| 9KW w/ RQE |
4 wires (56 suffix if power is doubled up, or 66 suffix with 2 unused 28AWG wires) |
| 45HW Power |
2 wires (54 suffix if power is doubled up, or 66 suffix with 4 unused 28AWG wires) |
| IDH MAX |
Always has 2 power wires and 2 data wires = 56 Suffix (if you double up the power wires) or 66 |
You will need a 2 additional 28AWG wires if the following sensors are called out on your model number:
- RQE
- DS
- LS.
- IDH* is a sensor option that would require 4 additional 28AWG wires)
*IDH = a sensor option for 45HW that adds both RQE and DS.
|
Electrical Ratings
| Suffix |
Number of Wires |
Wire Gage |
Volts (AC or DC) |
| |
|
|
6, 12, 24 |
48 |
| |
|
|
Current |
| -54 |
4 |
28 AWG |
1 amp/wire |
5 milli-amp/wire |
| -56 |
6 |
28 AWG |
.7 amp/wire |
5 milli-amp/wire |
| -58 |
8 |
28 AWG |
.5 amp/wire |
5 milli-amp/wire |
| -10 |
10 |
28 AWG |
.4 amp/wire |
5 milli-amp/wire |
| -66 |
6 |
2 @ 24 AWG |
2 amp/wire |
5 milli-amp/wire |
| 4 @ 28 AWG |
1amp/wire |
5 milli-amp/wire |
Inrush 15 A for .05 second/wire
"CE" hinges are listed by UL at these ratings
*Not available in FBB168 and FBB199
|