OnGuard Wi-Q Interface - Portals Will Not Come Online, New Install

Updated Jan 29, 2026

Complaint

  • Portals are set up in the System Administration.
  • Portals are configured.
  • Portals are not coming online.

Hint: Open the communication server and there is a device translation error when the portals are polled.

Issue

The BESTWiQInterfaceu.dll file failed to register at install.

Solution

Manually Register the WiQInterfaceu.dll.

  1. Stop the Lenel Communication server. 
  2. Run the CMD prompt as administrator and change the directory to C:\Windows\SysWOW64
  3. Enter the following line of text (...Exactly as you see it, including the double quotes):
    • regsvr32.exe "C:\Program Files (x86)\OnGuard\BESTWiQInterfaceu.dll"
  4. Hit the enter key and wait for the registration success message.
  5. Start the communication server as an application and verify the portals come online as well as the device translation error is no longer there. 

Applies To

Wi-Q Interface 3.02.007 for OnGuard 7.5, 7.6, and 8.0